Start a project

Lighting calculation assistant

Describe the room and the calculation writes itself

Give the room its dimensions and its purpose. The assistant sets the target illuminance, finds the total flux the room needs by the lumen method, and derives the luminaire count and the layout grid.

Calculation assistant

Four questions. At the end, a requirement sheet you can send to our engineering team.

    Step 1/4 What will the room be used for?

    The target illuminance, the glare limit and the colour rendering requirement all follow from this.

    The assistant runs in the browser and needs JavaScript. Send us your room dimensions through the contact form and we will run the calculation for you.

    Maintained target values for the EN 12464-1 space category. The edition in force governs.
    What will the room be used for? Illuminancelx UniformityUo Glare limitUGR Colour renderingRa Colour temperatureK
    Office, education, circulation
    Office, open plan 500 0.6 19 80 3500-4500
    Meeting room 500 0.6 19 80 3000-4000
    Classroom 300 0.6 19 80 4000-5000
    Technical drawing desk 750 0.7 16 80 4000-5000
    Archive, store room 200 0.4 25 80 3500-4500
    Corridor, circulation 100 0.4 28 40 3000-4000
    Stairs 150 0.4 25 40 3000-4000
    Washroom, WC 200 0.4 25 80 3000-4000
    Retail and hospitality
    Retail sales floor 300 0.4 22 80 3000-4000
    Checkout, counter 500 0.6 19 80 3000-4000
    Reception desk 300 0.6 22 80 3000-3500
    Lobby, waiting area * 200 0.4 22 80 2700-3000
    Restaurant, cafe floor * 200 0.4 22 90 2700-3000
    Commercial kitchen 500 0.6 22 80 4000-5000
    Sports hall, training 300 0.6 22 80 4000-5000
    Industry, storage, parking
    Rough assembly, fabrication 200 0.4 25 80 4000-5000
    Medium assembly work 300 0.6 22 80 4000-5000
    Fine assembly work 500 0.6 22 80 4000-5000
    Precision assembly, inspection 750 0.7 19 80 4000-5000
    Warehouse aisle, staffed 150 0.4 25 60 4000-5000
    Packing, dispatch 300 0.6 25 80 4000-5000
    Indoor car park 75 0.4 25 40 4000-5000
    Culture and care
    Museum, exhibition hall * 200 0.4 19 90 3000-3500
    Sensitive exhibits * 50 0.4 19 90 2700-3000
    Gallery, art space * 300 0.4 19 90 3000-4000
    Examination room 1000 0.6 19 90 4000-5000

    The standard sets no fixed value for this category. The figure below is a common design starting point and is settled per project. Colour temperature is a design decision, not a requirement of the standard.

    Lighting calculation

    Light is not estimated, it is calculated

    Luminaire count is not a preference, it is a result. Once room dimensions, surface reflectances, mounting height and target illuminance are on the table, the layout writes itself.

    300 lx 400 lx 500 lx 16.00 m 24° h 4.00 m Uo 0.60 UGR 19 Ra 90
    • Luminaire
    • Beam cone
    • Isolux contour
    The diagram shows how a lighting calculation is read. The figures are illustrative; every calculation is run against the project's own room model.
    Illuminance
    lx
    Light arriving at the working plane. The function of the space sets the target.
    Uniformity
    Uo
    Minimum over average. It keeps the eye reading the space without interruption.
    Glare
    UGR
    A measure of uncomfortable brightness in the direct field of view.
    Colour rendering
    Ra
    How truly colour reads under the light. Decisive in display and retail.
    Beam angle
    °
    The spread of the light. It separates accent from general lighting.
    Energy density
    W/m²
    Installed load per unit area. The indicator of efficiency and running cost.

    Let us buildthe spacetogether.

    Share your project, your drawings or your technical requirements. We will work out together where the light lands, at what angle and at what intensity.