Recessed downlight
The base interior luminaire, recessed into a suspended ceiling and directing light downward. Glare control is resolved through housing depth.
- Used in
- Interior, Hospitality, Museum and heritage
For project teams
We prepare the technical data an architect, interior designer, lighting designer, electrical engineer or contractor needs, on a per-project basis.
Lighting calculation
Luminaire count is not a preference, it is a result. Once room dimensions, surface reflectances, mounting height and target illuminance are on the table, the layout writes itself.
Luminaire types
The types below are grouped by how they distribute light and where they are mounted. Each card carries the distribution drawing and an example of that type from our catalogue.
None of these families is a fixed model list. Wattage, luminous flux, colour temperature, ingress rating and beam angle are set against the project's requirement, and the datasheet is issued to match.
The base interior luminaire, recessed into a suspended ceiling and directing light downward. Glare control is resolved through housing depth.
Accent luminaires whose position and aim can be changed later. The flexible side of display and retail layouts.
Takes the place of a suspended ceiling tile and spreads light from a large, low-luminance surface. The default answer in offices and teaching spaces.
Continuous runs that follow the architectural line. Can be recessed into reveals and niches.
A circular body lighting both downward and upward. The form itself becomes a geometric element of the room.
High-efficiency industrial luminaires covering large areas from tall mounting heights.
Aimable, sealed-housing luminaires that wash or accent the building envelope.
High-output sealed-body luminaire aimed at a target, in narrow or wide distributions. For facades, yards and sports areas.
Lights a route and its surroundings from the top of a column. Spacing and mounting height, not wattage, decide the uniformity.
Exterior luminaires at pedestrian height that keep light directed downward.
Walkable recessed luminaires that graze a surface or wash a vertical element from below.
Luminaires developed from scratch where the families above do not meet the requirement.
These documents are produced for the project and the selected luminaire rather than pulled from a standing archive. Send us your project and we will prepare the relevant files for you.
Housing, optical and mounting information for the selected product families.
Summary electrical and photometric data for the luminaire.
IES and LDT files for use in lighting calculation software.
Dimensioned two-dimensional drawing of the luminaire.
Parametric object for placement in the building information model.
Placement, supply and aiming instructions.
Installation
The following is general guidance. Electrical installation work must be carried out by a qualified electrician in accordance with the regulations in force.
Electric shock kills. No connection is made before the supply is isolated and the absence of voltage has been confirmed by measurement.
Drop the fuse or breaker for the circuit. Hang a warning label on the board and lock the breaker off where you can. Someone who does not know you are working can put it back on; the label is the only thing preventing that.
Switching off is not proof. Test your instrument on a known live point, then on the circuit you will work on, then on the known live point again. That final step is the only way you learn the instrument failed in between.
The common colour code is brown, black or grey for line, blue for neutral, green-and-yellow for the protective conductor. A colour code is an expectation, not a guarantee: in an old or altered installation, confirm by measurement before trusting it.
On Class I luminaires the conductive body must be bonded to the protective conductor. Connect earth first and remove it last, so the body is protected at every moment in between.
A loose terminal heats, and a hot terminal starts fires. No insulation inside the terminal, no bare copper outside it. Use ferrules on stranded conductors rather than clamping them like solid core.
On pendants and high bays the suspension fixes to structure, not to a ceiling tile or a grid profile. The cable is a conductor, not a support.
In wet rooms, outdoors and anywhere pressure-washed, the luminaire's IP rating has to meet the environment. The driver goes somewhere accessible and ventilated, never buried in insulation.
Review the connections and the insulation, measure the continuity of the body bond, refit covers and gaskets. If you will measure after energising, use appropriate personal protective equipment.
This text does not replace any luminaire's own installation document. The manual supplied with the product and the wiring regulations in force take precedence.
Selection
Price and wattage do not define a luminaire. The headings below are the values to look for on a datasheet, and the ones that cause trouble on site when they are skipped.
By sector
This table is the readable form of the reference data the calculation assistant runs on. Illuminance and colour rendering follow the EN 12464-1 space categories; colour temperature and luminaire type follow common design practice.
| Space | Illuminance | Colour temperature | Colour rendering | Suited luminaire |
|---|---|---|---|---|
| Office, education, circulation | ||||
| Office, open plan | 500 lx | 3500 - 4500 K | Ra 80 | Linear system, Recessed downlight |
| Meeting room | 500 lx | 3000 - 4000 K | Ra 80 | Recessed downlight, Linear system |
| Classroom | 300 lx | 4000 - 5000 K | Ra 80 | Linear system |
| Technical drawing desk | 750 lx | 4000 - 5000 K | Ra 80 | Linear system |
| Archive, store room | 200 lx | 3500 - 4500 K | Ra 80 | Linear system |
| Corridor, circulation | 100 lx | 3000 - 4000 K | Ra 40 | Recessed downlight, Linear system |
| Stairs | 150 lx | 3000 - 4000 K | Ra 40 | Recessed downlight |
| Washroom, WC | 200 lx | 3000 - 4000 K | Ra 80 | Recessed downlight |
| Retail and hospitality | ||||
| Retail sales floor | 300 lx | 3000 - 4000 K | Ra 80 | Track and spot, Recessed downlight |
| Checkout, counter | 500 lx | 3000 - 4000 K | Ra 80 | Recessed downlight, Linear system |
| Reception desk | 300 lx | 3000 - 3500 K | Ra 80 | Recessed downlight, Project-specific |
| Lobby, waiting area | 200 lx | 2700 - 3000 K | Ra 80 | Recessed downlight, Project-specific, Track and spot |
| Restaurant, cafe floor | 200 lx | 2700 - 3000 K | Ra 90 | Project-specific, Track and spot, Recessed downlight |
| Commercial kitchen | 500 lx | 4000 - 5000 K | Ra 80 | Linear system |
| Sports hall, training | 300 lx | 4000 - 5000 K | Ra 80 | High bay, Linear system |
| Industry, storage, parking | ||||
| Rough assembly, fabrication | 200 lx | 4000 - 5000 K | Ra 80 | High bay, Linear system |
| Medium assembly work | 300 lx | 4000 - 5000 K | Ra 80 | High bay, Linear system |
| Fine assembly work | 500 lx | 4000 - 5000 K | Ra 80 | Linear system, High bay |
| Precision assembly, inspection | 750 lx | 4000 - 5000 K | Ra 80 | Linear system |
| Warehouse aisle, staffed | 150 lx | 4000 - 5000 K | Ra 60 | High bay, Linear system |
| Packing, dispatch | 300 lx | 4000 - 5000 K | Ra 80 | Linear system, High bay |
| Indoor car park | 75 lx | 4000 - 5000 K | Ra 40 | Linear system |
| Culture and care | ||||
| Museum, exhibition hall | 200 lx | 3000 - 3500 K | Ra 90 | Track and spot, Recessed downlight |
| Sensitive exhibits | 50 lx | 2700 - 3000 K | Ra 90 | Track and spot |
| Gallery, art space | 300 lx | 3000 - 4000 K | Ra 90 | Track and spot, Linear system |
| Examination room | 1000 lx | 4000 - 5000 K | Ra 90 | Linear system, Recessed downlight |
Colour temperature and luminaire type are design decisions, not requirements of the standard. For illuminance and colour rendering, the edition of the standard in force governs.